Cyrix-Li-Charge 24/48V-120A
The price provided is NET-price, meaning shipment and VAT are not included. Additional duties and tax payments might be required. Taxes and delivery costs are calculated after ordering the goods and depend on the type of client and delivery address.
The Cyrix-Li-Charge facilitates a 3-second delayed connection between a battery charger and the system under the following conditions:
VE.Bus BMS Charge Disconnect Output is High:
- The connection occurs when the charge disconnect output of the VE.Bus BMS is high.
Voltage Sensing:
- It engages if it senses 13.0 V (or 26.0 V or 52.0 V) or more on its battery charger connection terminal.
- It engages if it senses 2 V or more on its battery terminal (remaining open if not connected to the battery).
The Cyrix-Li-Charge swiftly disengages if its control input becomes free-floating, indicating cell overvoltage or over-temperature. In the event of a cell overvoltage alarm, a reset occurs shortly after charging stops, allowing the Cyrix to reconnect the charger after a 3-second delay.
While engaged (charger connected to the battery), the Cyrix disengages after 1 hour to verify the charger's status. If, post-disengagement, the battery charger's output immediately increases to 13.0 V or more, the Cyrix reengages with a 3-second delay.
Note: If there is zero discharge current or a small discharge current, the Cyrix remains engaged shortly after the charger is switched off or disconnected, as the battery voltage remains higher than 13.5 V.
لم يتم العثور على أي تقييمات